packages/net/nut/files/nut-monitor.init
Daniel F. Dickinson a2f64b3bac nut: Reduce user error with POWERDOWNFLAG
Instead of making POWERDOWNFLAG an uci option the user can
only change it via initscript edits.  This avoids chance for users
to miss the required change to nut-driver when setting an UCI option
for nut-monitor which results in failure to do FSD on the UPS.

Signed-off-by: Daniel F. Dickinson <cshored@thecshore.com>
2018-08-29 00:17:19 -04:00

185 lines
5.1 KiB
Bash
Executable file

#!/bin/sh /etc/rc.common
START=60
USE_PROCD=1
UPSMON_C=/var/etc/nut/upsmon.conf
nut_upsmon_conf() {
local cfg="$1"
local RUNAS val optval
echo "# Config file automatically generated from UCI config" > $UPSMON_C
config_get RUNAS "$cfg" runas "nutmon"
[ -n "$RUNAS" ] && echo "RUN_AS_USER $RUNAS" >> "$UPSMON_C"
runas=$RUNAS
config_get val "$cfg" minsupplies 1
echo "MINSUPPLIES $val" >> $UPSMON_C
config_get val "$cfg" shutdowncmd "/usr/sbin/nutshutdown"
echo "SHUTDOWNCMD \"$val\"" >> $UPSMON_C
config_get val "$cfg" notifycmd
[ -n "$val" ] && echo "NOTIFYCMD \"$val\"" >> $UPSMON_C
config_get val "$cfg" pollfreq 5
echo "POLLFREQ $val" >> $UPSMON_C
config_get val "$cfg" pollfreqalert 5
echo "POLLFREQALERT $val" >> $UPSMON_C
config_get val "$cfg" hostsync 15
echo "HOSTSYNC $val" >> $UPSMON_C
config_get val "$cfg" deadtime 15
echo "DEADTIME $val" >> $UPSMON_C
echo "POWERDOWNFLAG /var/run/killpower" >> $UPSMON_C
config_get val "$cfg" onlinemsg
[ -n "$val" ] && echo "NOTIFYMSG ONLINE \"$val\"" >> $UPSMON_C
config_get val "$cfg" onbattmsg
[ -n "$val" ] && echo "NOTIFYMSG ONBATT \"$val\"" >> $UPSMON_C
config_get val "$cfg" lowbattmsg
[ -n "$val" ] && echo "NOTIFYMSG LOWBATT \"$val\"" >> $UPSMON_C
config_get val "$cfg" fsdmsg
[ -n "$val" ] && echo "NOTIFYMSG FSD \"$val\"" >> $UPSMON_C
config_get val "$cfg" commokmsg
[ -n "$val" ] && echo "NOTIFYMSG COMMOK \"$val\"" >> $UPSMON_C
config_get val "$cfg" commbadmsg
[ -n "$val" ] && echo "NOTIFYMSG COMMBAD \"$val\"" >> $UPSMON_C
config_get val "$cfg" shutdownmsg
[ -n "$val" ] && echo "NOTIFYMSG SHUTDOWN \"$val\"" >> $UPSMON_C
config_get val "$cfg" replbattmsg
[ -n "$val" ] && echo "NOTIFYMSG REPLBATT \"$val\"" >> $UPSMON_C
config_get val "$cfg" nocommmsg
[ -n "$val" ] && echo "NOTIFYMSG NOCOMM \"$val\"" >> $UPSMON_C
config_get val "$cfg" noparentmsg
[ -n "$val" ] && echo "NOTIFYMSG NOPARENT \"$val\"" >> $UPSMON_C
notifylist() {
local value="$1"
append optval "$value" "+"
}
setnotify() {
local cfg="$1"
local optname="$2"
local optval
config_list_foreach "$cfg" "$optname" notifylist
if [ -z "$optval" ]; then
# If no list fallback to trying option, fallback to default
config_get optval "$cfg" "$optname" "$default"
if [ -n "$optval" ]; then
echo "$optval"
else
# No default, so do the NUT default
echo "SYSLOG"
fi
else
echo "$optval"
fi
}
local default optval
val=""
config_list_foreach "$cfg" defaultnotify notifylist
default="$optval"
echo "NOTIFYFLAG ONLINE $(setnotify "$cfg" onlinenotify)" >> $UPSMON_C
echo "NOTIFYFLAG ONBATT $(setnotify "$cfg" onbattnotify)" >> $UPSMON_C
echo "NOTIFYFLAG LOWBATT $(setnotify "$cfg" lowbatnotify)" >> $UPSMON_C
echo "NOTIFYFLAG FSD $(setnotify "$cfg" fsdnotify)" >> $UPSMON_C
echo "NOTIFYFLAG COMMOK $(setnotify "$cfg" commoknotify)" >> $UPSMON_C
echo "NOTIFYFLAG COMMBAD $(setnotify "$cfg" commbadnotify)" >> $UPSMON_C
echo "NOTIFYFLAG SHUTDOWN $(setnotify "$cfg" shutdownnotify)" >> $UPSMON_C
echo "NOTIFYFLAG REPLBATT $(setnotify "$cfg" repolbattnotify)" >> $UPSMON_C
echo "NOTIFYFLAG NOCOMM $(setnotify "$cfg" nocommnotify)" >> $UPSMON_C
echo "NOTIFYFLAG NOPARENT $(setnotify "$cfg" noparentnotify)" >> $UPSMON_C
config_get val "$cfg" rbwarntime 43200
echo "RBWARNTIME $val" >> $UPSMON_C
config_get val "$cfg" nocommwarntime 300
echo "NOCOMMWARNTIME $val" >> $UPSMON_C
config_get val "$cfg" finaldelay 5
echo "FINALDELAY $val" >> $UPSMON_C
config_get val "$cfg" certpath
if [ -n "$val" ]; then echo "CERTPATH $val" >> $UPSMON_C; fi
config_get_bool val "$cfg" certverify 0
if [ -n "$val" ]; then echo "CERTVERIFY $val" >> $UPSMON_C; fi
config_get_bool val "$cfg" forcessl 0
if [ -n "$val" ]; then echo "FORCESSL $val" >> $UPSMON_C; fi
}
nut_upsmon_add() {
local cfg="$1"
local type="$2"
local upsname
local hostname
local port
local powervalue
local username
local password
local system
config_get upsname "$cfg" upsname
config_get hostname "$cfg" hostname localhost
config_get port "$cfg" port
config_get powervalue "$cfg" powervalue 1
config_get username "$cfg" username
config_get password "$cfg" password
system="$upsname@$hostname"
if [ -n "$port" ]; then
system="$system:$port";
fi
echo "MONITOR $system $powervalue $username $password $type" >> $UPSMON_C
}
build_config() {
local runas
mkdir -m 0750 -p "$(dirname "$UPSMON_C")"
config_load nut_monitor
config_foreach nut_upsmon_conf upsmon
config_foreach nut_upsmon_add master master
config_foreach nut_upsmon_add slave slave
[ -z "$(cat /var/etc/nut/nut.conf)" ] && {
echo "MODE=netclient" >>/var/etc/nut/nut.conf
chmod 640 /var/etc/nut/nut.conf
chgrp $(id -gn ${runas:-root}) /var/etc/nut/nut.conf
}
chmod 640 "$UPSMON_C"
chgrp $(id -gn ${runas:-root}) "$UPSMON_C"
}
start_service() {
build_config
procd_open_instance
procd_set_param respawn
procd_set_param stderr 0
procd_set_param stdout 1
procd_set_param command /usr/sbin/upsmon -D
procd_close_instance
}
reload_service() {
if pgrep upsmon >/dev/null 2>/dev/null; then
build_config
upsmon -c reload
else
stop
sleep 1
start
fi
}
service_triggers() {
procd_add_reload_trigger nut_monitor
}